HIL-1611

5

HIL-1611

Message

MISMATCH in PSU-FAN Air Flow direction. Replace PSU with fan air flows in same
direction. System will be shut down in 2 minutes.

Message Type

FFDC | LOG

Severity

CRITICAL

Probable Cause

Indicates that the airflows of the power supply and fan assemblies are moving in the reverse or opposite
direction, which could overheat the system. The airflow of the power supply and fan assemblies must
move in the same direction or the system will shut down in two minutes. This message is applicable only
to the Brocade 6510.

Recommended

Action

Use the chassisShow command to check the airflow directions of the power supply and fan assemblies.
Ensure that the airflows run in the same direction.

HIL-1612

Message

MISMATCH in PSU-FAN Air Flow direction. System shut down.

Message Type

LOG

Severity

CRITICAL

Probable Cause

Indicates that the airflows of the power supply and fan assemblies are moving in the reverse or opposite
direction. The system will shut down immediately. This message is applicable only to the Brocade 6510.

Recommended

Action

Ensure that the airflows of the power supply and fan assemblies run in the same direction.

HIL-1613

Message

PSU-FAN FRUS Air Flow matched. System shutdown canceled.

Message Type

LOG

Severity

INFO

Probable Cause

Indicates that the airflows of the power supply and fan assemblies have changed to move in the same
direction. The system continues to operate. This message is applicable only to the Brocade 6510.

Recommended

Action

Ensure that the airflows of the power supply and fan assemblies run in the same direction.