Fabric OS Message Reference
53-1002749-01
HIL-1603
5
HIL-1603
Message
Message Type
FFDC | LOG
Severity
CRITICAL
Probable Cause
Indicates that the total fan failure count is greater than or equal to two.
Recommended
Action
To avoid causing damage to the switch, the system shuts down automatically. To help prevent future
problems, make sure that all the fans are working properly.
HIL-1605
Message
High temperature (
environmental specifications.
Message Type
LOG
Severity
INFO
Probable Cause
Indicates that temperatures in the system have risen above the threshold and that the fan speed is being
increased.
Recommended
Action
No action is required.
HIL-1610
Message
Fan/PS unit
may not be available. Please ensure that the unit has power and the switch is on.
Message Type
LOG
Severity
WARNING
Probable Cause
Indicates that the power supply is not connected to a power source, is not switched on, or the unit is
faulty. This message is applicable only to the Brocade 5100.
Recommended
Action
Ensure the power cord is connected to the unit with a valid power source and then switch on the unit. If
the problem persists, try reseating the unit. If the problem still persists, replace the FRU.