Hil-1403, Hil-1404, Hil-1501 – Dell POWEREDGE M1000E User Manual
Page 579
Fabric OS Message Reference
557
53-1002749-01
HIL-1403
5
HIL-1403
Message
All fan FRUs missing. Install fan FRUs immediately.
Message Type
LOG
Severity
WARNING
Probable Cause
Indicates that all fan field-replaceable units (FRUs) have been removed.
Recommended
Action
Install the missing fan FRUs immediately.
HIL-1404
Message
Message Type
LOG
Severity
WARNING
Probable Cause
Indicates that one or more fan field-replaceable units (FRUs) have been removed.
Recommended
Action
Install the missing fan FRUs immediately.
HIL-1501
Message
Slot
Message Type
LOG
Severity
WARNING
Probable Cause
Indicates that the temperature of this blade has risen above the warning threshold.
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well-ventilated and that the room temperature is within operational range of
your switch. Refer to the hardware reference manual for your switch for the operational temperature
range.