Fabric OS Message Reference

551

53-1002749-01

HIL-1202

5

HIL-1202

Message

Blower faulted, speed ( RPM) below threshold.

Message Type

LOG

Severity

ERROR

Probable Cause

Indicates that the specified fan speed (in RPM) has fallen below the minimum threshold.

Recommended

Action

Replace the fan FRU.

HIL-1203

Message

Fan faulted, speed ( RPM) above threshold.

Message Type

LOG

Severity

ERROR

Probable Cause

Indicates that the specified fan speed (in RPM) has risen above the maximum threshold. A high speed
does not necessarily mean that the fan is faulty.

Recommended

Action

Run the tempShow command to verify that the switch temperatures are within operational ranges. Refer
to the hardware reference manual for the temperature range of your switch.

Make sure that the area is well-ventilated and that the room temperature is within the operational range
of your switch. Refer to the hardware reference manual for your switch for the operational temperature
range.

Run the fanShow command to monitor the speed of the fan generating this error.

If the fan continues to generate this message, replace the fan FRU.

HIL-1204

Message

Fan faulted, speed ( RPM) below threshold.

Message Type

LOG

Severity

ERROR

Probable Cause

Indicates that the specified fan speed (in RPM) has fallen below the minimum threshold. This message is
specific to non-bladed switches.

Recommended

Action

Replace the fan field-replaceable unit (FRU).

For switches that do not have FRUs, replace the entire switch.