Hil-1301, Hil-1302, Hil-1303 – Dell POWEREDGE M1000E User Manual
Page 575
Fabric OS Message Reference
553
53-1002749-01
HIL-1301
5
HIL-1301
Message
1 blower failed or missing. Replace failed or missing blower assembly immediately.
Message Type
LOG
Severity
WARNING
Probable Cause
Indicates that a fan field-replaceable unit (FRU) has failed or has been removed. This message is often
preceded by a low speed error message. This problem can cause the switch to overheat.
Recommended
Action
Replace the affected fan FRU immediately.
HIL-1302
Message
immediately.
Message Type
LOG
Severity
WARNING
Probable Cause
Indicates that multiple fan field-replaceable units (FRUs) have failed or are missing on a switch. This
message is often preceded by a low fan speed message.
Recommended
Action
Replace the affected fan FRUs immediately.
HIL-1303
Message
One fan failed. Replace failed fan FRU immediately.
Message Type
LOG
Severity
ERROR
Probable Cause
Indicates that a fan field-replaceable unit (FRU) has failed. This message is often preceded by a low fan
speed message.
Recommended
Action
Replace the faulty fan FRU immediately.