Configure basic device, Parameters, Configure advanced parameters – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual
Page 70: Configure basic device parameters
70
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 3 Energy Data Collector Configuration
The Ethernet communication parameters are listed in this table.
4.
To change a parameter:
a. Press Enter to select a menu item.
b. Press the Up and Down arrows to change the value.
c. When the desired value is displayed, press Enter to confirm your selection.
5.
Press Esc
to return to the main menu.
Configure Basic Device Parameters
1.
From the main programming menu, use the Up and Down Arrows to scroll through the programming menu and
view the configuration for the basic device parameters.
2.
To change a parameter:
a. Press Enter to select a menu item.
b. Press the Up and Down arrows to change the value.
c. When the desired value is displayed, press Enter to confirm your selection.
3.
Press Esc to return to the main menu.
Configure Advanced Parameters
Follow these steps to configure the advanced parameters for the PowerMonitor 500 device. These settings include the
demand calculation mode, interval time, and synchronization mode.
1.
From the main programming menu, use the Up and Down Arrows to scroll through the programming menu.
2.
Select a menu item by pressing Enter.
Parameter
Range
Default
IP Address
www.xxx.yyy.zzz
N/A
Subnet
www.xxx.yyy.zzz
N/A
Gateway
www.xxx.yyy.zzz
N/A
TCP IP Port
1…9999
502
ACD
Yes or No
No
Parameter
Range
Default
System
1P, 2P, 3P, 3P.n,3P.1, 3P.2
3P.n
CT Ratio
1.0…9999
1.0
PT Ratio
1.0…9999
1.0