70

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

Chapter 3 Energy Data Collector Configuration

The Ethernet communication parameters are listed in this table.

4.

To change a parameter:
a. Press Enter to select a menu item.
b. Press the Up and Down arrows to change the value.
c. When the desired value is displayed, press Enter to confirm your selection.

5.

Press Esc

to return to the main menu.

Configure Basic Device Parameters

1.

From the main programming menu, use the Up and Down Arrows to scroll through the programming menu and
view the configuration for the basic device parameters.

2.

To change a parameter:
a. Press Enter to select a menu item.
b. Press the Up and Down arrows to change the value.
c. When the desired value is displayed, press Enter to confirm your selection.

3.

Press Esc to return to the main menu.

Configure Advanced Parameters

Follow these steps to configure the advanced parameters for the PowerMonitor 500 device. These settings include the
demand calculation mode, interval time, and synchronization mode.

1.

From the main programming menu, use the Up and Down Arrows to scroll through the programming menu.

2.

Select a menu item by pressing Enter.

Parameter

Range

Default

IP Address

www.xxx.yyy.zzz

N/A

Subnet

www.xxx.yyy.zzz

N/A

Gateway

www.xxx.yyy.zzz

N/A

TCP IP Port

1…9999

502

ACD

Yes or No

No

Parameter

Range

Default

System

1P, 2P, 3P, 3P.n,3P.1, 3P.2

3P.n

CT Ratio

1.0…9999

1.0

PT Ratio

1.0…9999

1.0