beautypg.com

Configure load inputs and outputs – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual

Page 366

background image

366

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

Chapter 12 Demand Control

Configure Load Inputs and Outputs

Follow these steps to load inputs and outputs.

1.

Expand the DemandControl program and double-click the SR00_IO_Mapping Routine.

2.

Rungs 1 through 32 have been configured for I/O mapping.

The I/O mapping routine will not be executed unless the Enable_IO bit is set. Refer to

page 379

,

step 10

.

For each load, there are two rungs to configure. The first is for mapping the command output.

3.

Double-click the NOP instruction on rung 1 and type OTE.

4.

Click Enter.

5.

Double click on the question mark above the OTE and type the name of the tag that should be mapped to the output
command for Load Number 1.

Use an XIC/XIO or an OTE/OTU instruction as required to fit your application.

In the Efficient Industries example, the output for Load 1 is hard-wired to Local:2:O.Data.0.

6.

Click Enter.

In rung 2, the input status has been configured to follow the commanded state. If the input status is not available for
the load, this rung can be left alone. In the Efficient Industries example, the input status for Load number 1 is
available and is hard-wired to Local:1:I.Data.0.

7.

Double click the tag above the XIC instruction and enter the tag for the input status.

Use an XIO or an XIC instruction as required to fit your application.