Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

Chapter 11

FactoryTalk View ME Energy Faceplates

7. Open the Parameter List and modify as your application requires.

In addition to application required parameters, the following parameter settings must be applied for general
Ethernet/IP network communication for the PowerFlex drive faceplates to operate correctly.
a. For the PowerFlex 70, 70EC, 700, 700VC, and 700H drives, set parameter 90 to DPI Port 5 (22).

b. For the PowerFlex 700S drives, set parameter 16 to Spd Ref DPI (6) and parameter 691 to Int DPI Comm (5).

c. For the PowerFlex 700S 2P drives, set parameter 27 to DPI Port 5 (16).

d. For the PowerFlex 753 drives, verify that parameter 545 Spd Ref A Sel is set to Port 0: Port 6 Reference and the

value is set to 876.

8. Close the Parameter List window.

9. Download your parameters to the PowerFlex drive by choosing the download icon from the toolbar.

Follow prompts to complete the download process.