Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

Chapter 11

FactoryTalk View ME Energy Faceplates

Add Alarm History Faceplate Display

Follow these steps to add the Alarm History Faceplate display to your FactoryTalk View ME application. The procedure
uses the

Efficient Industries Plant 1

example to demonstrate the configuration steps.

1. Open the FactoryTalk View ME application to which you want to add the Alarm History Faceplate.

2. Right-click Displays and choose Add Component Into

Application.

3. Browse to the Faceplate Files folder on your

Energy Management Toolkit CD image and
select the ME Alarm History Faceplate Files
folder.

4. Select the Alarm History.gfx file and click

Open.

5. Verify Alarm History appears under Displays.

TIP

The default display size for the Alarm History Faceplate is 640 x 480 and is compatible with PanelView Plus
700 or larger terminals.