Chapter 9 FactoryTalk EnergyMetrix Software Reports and Charts
Power Quality Report
A power quality report combines a graph and grid display of power quality (sag and swell) events. FactoryTalk
EnergyMetrix software periodically reads the power monitor event log from the PowerMonitor 3000, and stores sag and
swell events in the database. The power quality report displays events logged during the selected report interval on a ITI/
CBEMA chart and in a grid (tabular) listing.
example, you will create a power quality report for the PowerMonitor 3000 Electric
Main meter.
Create and View Report
Follow these steps to set up and view a power quality report.
1.
Click the Reports tab.
2.
Navigate to and select a domain for the report.
For this example, select Engineering.
Only users with access to the domain will be
able to view the report.
3.
Click Add.
4.
Enter a Report name.
For this example, enter Electric Main
Power Quality Report.
5.
Choose the Power Quality template.
6.
Accept the default Report file.
7.
Verify the Report parent group.
For this example, Engineering was
selected in step 2.
8.
Select the meters or groups to include in
the report.
For this example, check the Electric Main
meter.
9.
Click Save.
TIP
The power quality report is supported only for PowerMonitor 3000 M6/M8 models with configured sag and swell
setpoints. Enable PQ events logging must be checked when configuring the device.