Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

409

Time of Day Control Chapter 13

System Startup and Test

Configure the individual loads and the time of day schedule.

Setup

1.

Verify the TOD controller is in Run mode.

2.

Verify the HMI application is running on the PanelView
Plus Terminal.

3.

Verify the IO Mapping rungs in the controller are
enabled.
a. Go online with your RSLogix project and monitor the

Enable_IO tag.

b. Set the tag value to ‘1’ if it is not already set.

Configure Time and Date

1.

From the TOD faceplate, click the configuration button
on the toolbar.

2.

Verify the current date and time.

If the current date and time are correct, no action is
required. If the current date and time are not correct, click
the time and date configuration button on the toolbar.

3.

Enter the current time and date.

4.

Choose an option for Daylight Savings Time.

5.

Click on the box to toggle between Yes (apply) and No
(do not apply).

6.

Click Update PLC Clock.