The Load UDT is used to store the main load attributes for each load.
Name
Data Type
Description
Name
STRING
Load Description
Number
DINT
Load Number
Priority
DINT
Load Priority 1…16 (Priority 16 loads are shed
first)
kW_Rated
DINT
User Input (0…65535)
kWh_Sheddable
DINT
kW_Rated * PM.Period_Remaining_Sec/3600
Inp_Status
BOOL
Status of load from discrete input 0=Off 1=On
Avail
BOOL
0=Override, 1=Normal
Shed_State
BOOL
Shed (on) Normal (off)
Out_Shed
BOOL
1=Shed Load
Intlk_State
BOOL
1=Interlocked (Load not available to shed)
Intlk_Bypass
BOOL
User command to bypass all interlocks
Alm_FailToShed
BOOL
Load Shed Failed Alarm
Val_Status
DINT
Status Value used to drive status indicators on
the faceplate
Off_Delay_Sec
DINT
Min time on before shedding User Input
(0…3600 s)
On_Delay_Sec
DINT
Min time off before restarting User Input
(0…3600 s)
Max_Off_Time_Sec
DINT
Max time per hour shed User input (0…3600 s)
Alm_DelayTimer
TIMER
Failed to Shed Alarm Delay Timer
Off_Delay_Timer
TIMER
Min time on before shedding timer
On_Delay_Timer
TIMER
Min time off before restarting timer
OneHourTimer
TIMER
Rolling One Hour Timer to limit the amount of
time per hour the load is shed
Max_Off_Timer
TIMER
Maximum Off (Shed) timer
Min_Since_Shed_Timer
TIMER
One minute timer used to count the minutes
since shed
Minutes_Since_Shed
COUNTER
Incremented each time the minutes since shed
timer is done
storagebits
BOOL[32]
Miscellaneous storage bits used for
programming