Chapter 12 Demand Control

The Load UDT is used to store the main load attributes for each load.

Name

Data Type

Description

Name

STRING

Load Description

Number

DINT

Load Number

Priority

DINT

Load Priority 1…16 (Priority 16 loads are shed

first)

kW_Rated

DINT

User Input (0…65535)

kWh_Sheddable

DINT

kW_Rated * PM.Period_Remaining_Sec/3600

Inp_Status

BOOL

Status of load from discrete input 0=Off 1=On

Avail

BOOL

0=Override, 1=Normal

Shed_State

BOOL

Shed (on) Normal (off)

Out_Shed

BOOL

1=Shed Load

Intlk_State

BOOL

1=Interlocked (Load not available to shed)

Intlk_Bypass

BOOL

User command to bypass all interlocks

Alm_FailToShed

BOOL

Load Shed Failed Alarm

Val_Status

DINT

Status Value used to drive status indicators on

the faceplate

Off_Delay_Sec

DINT

Min time on before shedding User Input

(0…3600 s)

On_Delay_Sec

DINT

Min time off before restarting User Input

(0…3600 s)

Max_Off_Time_Sec

DINT

Max time per hour shed User input (0…3600 s)

Alm_DelayTimer

TIMER

Failed to Shed Alarm Delay Timer

Off_Delay_Timer

TIMER

Min time on before shedding timer

On_Delay_Timer

TIMER

Min time off before restarting timer

OneHourTimer

TIMER

Rolling One Hour Timer to limit the amount of

time per hour the load is shed

Max_Off_Timer

TIMER

Maximum Off (Shed) timer

Min_Since_Shed_Timer

TIMER

One minute timer used to count the minutes

since shed

Minutes_Since_Shed

COUNTER

Incremented each time the minutes since shed

timer is done

storagebits

BOOL[32]

Miscellaneous storage bits used for

programming