beautypg.com

Follow these steps, Control hardware selection and wiring, List load outputs and inputs – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual

Page 394

background image

394

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

Chapter 13 Time of Day Control

Follow These Steps

The following steps are based on a CompactLogix 1769-L23E-QBFC1 packaged controller, but the general steps may be
applied to other Logix controller configurations and are similar. Follow these steps to implement your Time of Day Control
application:

Control Hardware Selection and Wiring
Logic Integration
HMI Integration
System Commissioning

Control Hardware Selection and Wiring

You need to determine what your system will contain.

List Load Outputs and Inputs

1.

Determine which loads in your application will be controlled by the Time of Day controller (maximum of 16 loads).

2.

Number each load from 1…16.

3.

List the outputs and inputs associated with each load.

As a minimum each load must accept a command to run from the Time of Day Controller. The Time of Day
Controller will also accept a load status input that can be used for indication and alarming, however this is not
required.

In the Efficient Industries Plant 1 example, the monitoring and analysis revealed some significant energy savings if
TOD control was used to control the loads identified below:

Load Number

Loads

Output Description

Output I/O Location

Input Description

Input I/O Location

1

Boiler 1

Command On

Local:2:O.Data.0

Status Feedback

Local:1:I.Data.0

2

Boiler 2

Command On

Local:2:O.Data.1

Status Feedback

Local:1:I.Data.1

3

Air Compressor 1

Command On

Local:2:O.Data.2

Status Feedback

Local:1:I.Data.2

4

Air Compressor 2

Command On

Local:2:O.Data.3

Status Feedback

Local:1:I.Data.3

5

Air Compressor 3

Command On

Local:2:O.Data.4

Status Feedback

Local:1:I.Data.4

6

Lighting Production

Area 1

Command On

Local:2:O.Data.5

Status Feedback

Local:1:I.Data.5

7

Lighting Production

Area 2

Command On

Local:2:O.Data.6

Status Feedback

Local:1:I.Data.6

8

Lighting Shipping/

Receiving

Command On

Local:2:O.Data.7

Status Feedback

Local:1:I.Data.7

9

Lighting Office

Command On

Local:2:O.Data.8

N/A

N/A