Chapter 12 Demand Control

Load Status View

Click the Loads 1-8 or Loads 9-16 button on the toolbar to display the Load Status view. The Load 1-8 and Load 9-16
Status views display the load status, just like the Home View, as well as the load's rated kW, priority and description.

Faceplate Toolbar

Load Status

Button

Icons

Description

Alarm

The alarm button indicates an alarm condition and activates alarm diagnostic views. A grey bell indicates normal

status, with no alarms. A red flashing bell indicates an alarm condition.

Home

The Home button lets you view the status of all 16 loads.

Configuration

The Configuration button displays the main demand control configuration screen (upon entering the correct

password).

Help

The Help button provides information for the existing view.

Close

Click the Close button to close the faceplate.

Status Indicators

Grey - Off/Normal Control

Green - On/Normal Control
D-Grey - Off/Demand Control
OVR-Grey - Override Set
OVR-Green - On/Override Set
OVR-Red - On/Override Set/Operator Action Required
Red Flashing - Load is not in OVR, controller telling to turn off, but load is still on
INT-Green - Interlocked On
INT-Grey - Interlocked Off

Interlocks

Bypassed

Indicates that the interlocks have been bypassed for the load.

Load Number

The load number. To change the configuration for a load, click on the load number to launch the load configuration

screen.

Load Priority

The priority currently assigned to the load.

Load Rated KW

The rated kW currently assigned to the load.

Load Description

The description currently assigned to the load.