Load status view – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual
Page 384
384
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 12 Demand Control
Load Status View
Click the Loads 1-8 or Loads 9-16 button on the toolbar to display the Load Status view. The Load 1-8 and Load 9-16
Status views display the load status, just like the Home View, as well as the load's rated kW, priority and description.
Faceplate Toolbar
Load Status
Button
Icons
Description
Alarm
The alarm button indicates an alarm condition and activates alarm diagnostic views. A grey bell indicates normal
status, with no alarms. A red flashing bell indicates an alarm condition.
Home
The Home button lets you view the status of all 16 loads.
Configuration
The Configuration button displays the main demand control configuration screen (upon entering the correct
password).
Help
The Help button provides information for the existing view.
Close
Click the Close button to close the faceplate.
Status Indicators
Grey - Off/Normal Control
Green - On/Normal Control
D-Grey - Off/Demand Control
OVR-Grey - Override Set
OVR-Green - On/Override Set
OVR-Red - On/Override Set/Operator Action Required
Red Flashing - Load is not in OVR, controller telling to turn off, but load is still on
INT-Green - Interlocked On
INT-Grey - Interlocked Off
Interlocks
Bypassed
Indicates that the interlocks have been bypassed for the load.
Load Number
The load number. To change the configuration for a load, click on the load number to launch the load configuration
screen.
Load Priority
The priority currently assigned to the load.
Load Rated KW
The rated kW currently assigned to the load.
Load Description
The description currently assigned to the load.