Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

39

System Configuration and Wiring Chapter 2

6.

Identify other small groups (<3) of digital energy points in close proximity that can be collected by the digital status
inputs of the PowerMonitor 1000 device.
This is a lower cost alternative to a CompactLogix™ controller with a few digital inputs.

For the Efficient Industries Plant 1 example, the gas main and water main digital meters are somewhat isolated in the
corner of the production area near MCC 2. A PowerMonitor 1000 named MCC 2 is added to capture these two
digital meter inputs.

7.

Select a Device Class and Meter Type on the FactoryTalk EnergyMetrix tab of the Energy Data Worksheet for the
PowerMonitor status inputs identified in step 6.
a. Select a PowerMonitor 1000 Device Class.
b. Select PM Status Input for the Meter Type.

For the Efficient Industries Plant 1 example, the entries for the gas main and water main data points would look like
this.

8.

Identify other larger groups of digital and analog energy data points in close proximity that can connect to an L23
CompactLogix controller data collection device.