Demand Control Chapter 12

Program Overview

The Demand Control program is organized into eight routines, as shown below.

.

Routine Name

Description

MainRoutine

Performs the demand control calculations and processes the commands from the faceplate. It also dispatches all of the

subroutines.

SR00_IO_Mapping

Used to map the demand control inputs (Load[#].Inp_Status) and outputs (Load[#].Out_Shed) to the corresponding

hardwired I/O point or device level control tag for each load. This routine will need to be customized for each application, as

described on the next page.

SR01_ProcessPM1000

Reads the PowerMonitor 1000 device data and writes the data to the PM tag (UDT).

SR01_ProcessPM5000

Reads the PowerMonitor 5000 device data and writes the data to the PM tag (UDT).

SR02_ProcessLoads

Calculates the KWH_Sheddable, processes the timers, determines the inlerlock state, output state, and load status for the

load.

SR03_EvaluateLoads

Determines which loads are sheddable and copies the data for the sheddable loads into an array for sorting. This routine is

executed after each shed or restore event and periodically every 10 seconds.

SR04_Sort

Sorts the sheddable loads first by priority and then by minutes since shed ascending and stores them in the

Sheddable_Load LIFO array. This array presents the next load to shed as the last element in the array.

SR05_Shed

Sets the shed status equal to ‘Shed’ for the next load to shed. Adds the load to the Shed_Load FIFO array. This array

presents the next load to restore as the first element in the array.

SR06_Restore

Sets the shed status equal to ‘Normal’ for the next load to restore (the first element in the Shed_Load array).

SR07_ProcessAlarms

Sets the alarm status bit for the following alarms:

Power monitor communication loss

Invalid Power monitor Demand Configuration

Insufficient Sheddable Load

[Load Name] Load Shed Failed alarm

Only 1 Sheddable Load Available