Demand controller tags – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual
Page 389
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
389
Demand Control Chapter 12
Demand Controller Tags
When the DemandControl program is imported, three User Defined Data Types will be added to the controller;
DemandFaceplate, Load, and PM.
The DemandFaceplate UDT is used for the HMI interface.
Name
Data Type
Description
Set_FaceplateAnimation
INT
Controls the visibility on the faceplate
Set_LoadNum
DINT
Load number currently being configured
Set_Password
STRING
Password entered from the HMI
Cfg_Load
Load
Configured Load Buffer
Cfg_Password
STRING
Configured Password
Cfg_StartHour
DINT
Configured Demand Control Start Hour
Cfg_StartMin
DINT
Configured Demand Control Start Minute
Cfg_StopHour
DINT
Configured Demand Control Stop Hour
Cfg_StopMin
DINT
Configured Demand Control Stop Minute
Cfg_PeakDays
BOOL[32]
Configured Peak Days of the week
Cmd_PasswordEntered
DINT
Set when a password is entered from the
faceplate (Bit 0 is set when a password is
entered for demand control configuration, bits
1…16 are set when a password is entered for
configuring a specific load)
Cmd_SetPriority
BOOL
Set when a new priority is entered from the load
configuration screen
Cmd_SetKWRated
BOOL
Set when a new KW rating is entered from the
load configuration screen
Cmd_SetDesc
BOOL
Set when a new load description is entered from
the load configuration screen
Cmd_SetOnDelay
BOOL
Set when a new on delay time is entered from
the load configuration screen
Cmd_SetOffDelay
BOOL
Set when a new off delay time is entered from
the load configuration screen
Cmd_SetMaxOffTime
BOOL
Set when a new maximum off time is entered
from the load configuration screen
Sts_PasswordAccepted
BOOL
Set when the correct password is entered from
the faceplate, allowing visibility of the
configuration screen
Sts_BillingKW
DINT
Used for color animation of the present billing
kW
Sts_PredKW
DINT
Used for color animation of the predicted kW
demand
Val_ActiveAlarm
DINT
Used for displaying the highest priority alarm on
the faceplate
Val_AlmLabel
STRING
Used for displaying the load name on the
faceplate when the load shed failed alarm is
active