beautypg.com

Demand controller tags – Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual

Page 389

background image

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

389

Demand Control Chapter 12

Demand Controller Tags

When the DemandControl program is imported, three User Defined Data Types will be added to the controller;
DemandFaceplate, Load, and PM.

The DemandFaceplate UDT is used for the HMI interface.

Name

Data Type

Description

Set_FaceplateAnimation

INT

Controls the visibility on the faceplate

Set_LoadNum

DINT

Load number currently being configured

Set_Password

STRING

Password entered from the HMI

Cfg_Load

Load

Configured Load Buffer

Cfg_Password

STRING

Configured Password

Cfg_StartHour

DINT

Configured Demand Control Start Hour

Cfg_StartMin

DINT

Configured Demand Control Start Minute

Cfg_StopHour

DINT

Configured Demand Control Stop Hour

Cfg_StopMin

DINT

Configured Demand Control Stop Minute

Cfg_PeakDays

BOOL[32]

Configured Peak Days of the week

Cmd_PasswordEntered

DINT

Set when a password is entered from the

faceplate (Bit 0 is set when a password is

entered for demand control configuration, bits

1…16 are set when a password is entered for

configuring a specific load)

Cmd_SetPriority

BOOL

Set when a new priority is entered from the load

configuration screen

Cmd_SetKWRated

BOOL

Set when a new KW rating is entered from the

load configuration screen

Cmd_SetDesc

BOOL

Set when a new load description is entered from

the load configuration screen

Cmd_SetOnDelay

BOOL

Set when a new on delay time is entered from

the load configuration screen

Cmd_SetOffDelay

BOOL

Set when a new off delay time is entered from

the load configuration screen

Cmd_SetMaxOffTime

BOOL

Set when a new maximum off time is entered

from the load configuration screen

Sts_PasswordAccepted

BOOL

Set when the correct password is entered from

the faceplate, allowing visibility of the

configuration screen

Sts_BillingKW

DINT

Used for color animation of the present billing

kW

Sts_PredKW

DINT

Used for color animation of the predicted kW

demand

Val_ActiveAlarm

DINT

Used for displaying the highest priority alarm on

the faceplate

Val_AlmLabel

STRING

Used for displaying the load name on the

faceplate when the load shed failed alarm is

active