beautypg.com

Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual

Page 321

background image

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

321

FactoryTalk View ME Energy Faceplates

Chapter 11

5. Click OK to accept the default setup for the new

PowerMonitor tag.

The PowerMonitor Add-On Instructions use
explicit messaging to retrieve data from
PowerMonitor devices. You must configure an
explicit message for each PowerMonitor data
address. Four messages will be configured to display
PowerMonitor device values on the Equipment
Status and Alarm History faceplates. The table lists
the data and corresponding Add-On Instruction
parameters, tags, and addresses to be configured for
each device.

6. Select the message tag name field next to the

Ref_Total_Real_Power parameter and type a tag name in the
format x

xx_MsgTotalRealPower.

For this example Electric_Main_MsgTotalRealPower is
entered.

7. Right-click the message tag name just entered and choose New

xxx_MsgTotalRealPower’.

For this example, New ‘Electric_Main_MsgTotalRealPower’ is
selected.

Table 3 - PowerMonitor Add-On Instruction Tag References

PowerMonitor Data

Add-On Instruction
Parameter Tags

Message Tag

PLC5 Address

Message Destination Tag

PowerMonitor
1000

PowerMonitor
3000

Real Power

Ref_Total_Real_Power
Val_Total_Real_Power

xxx

(1)

_MsgTotalRealPower

(1) xxx is the PowerMonitor device name. For example, the prefix Electric_Main in Electric_Main_MsgTotalRealPower is the message tag for the PM 3000 Electric_Main device.

F22:7

F17:3

xxx(1)_TotalRealPowe
r

Average L-L Volts

Ref_Avg_L_L_Volts
Val_Avg_L_L_Volts

xxx(1)_MsgAvgLLVolts

F21:11

F15:11

xxx(1)_AvgLLVolts

Average Current

Ref_Avg_Current
Val_Avg_Current

xxx(1)_MsgAvgCurrent

F21:3

F15:3

xxx(1)_AvgCurrent

True Power Factor

Ref_True_Power_Factor
Val_True_Power_Factor

xxx(1)_MsgTruePowerFa
ctor

F22:3

F19:3

xxx(1)_TruePowerFact
or