Energy Data Collector Configuration Chapter 3
When the cursor is beneath the last digit on the left, a
further press of Escape (6) lets you change the decimal point
and the multiplier (9) (k or M). The blinking ‘dP’ (decimal
point) text (10) indicates this capability.
To modify the decimal point position and the multiplier, use
the Up and Down arrow button (7) to select the desired
value.
To store the new programmed value, press Enter (7). To
cancel the change in programming and restore the previous
values of the parameter, press Escape (6) for at least 2
seconds.
Follow these steps to configure PowerMonitor 500 device parameters.
Access the Programming Menu
1.
Press and hold Enter
for at least 2 seconds to access the programming menu.
2.
Enter the default password of 0 (or another valid password).
3.
Press Enter to access programming mode.
Configure Communication Parameters
1.
Press the Up Arrow until you reach the RS232-485 or Ethernet menu.
2.
Press Enter to select the menu item.
3.
Press the Up and Down arrows to scroll through the communication parameters.
The Serial communication parameters are listed in this table.
Parameter
Range
Default
Address
1…247
1
Communication Rate
9600, 19200, 38400, 115200
9600
Parity
None/odd/even
none