Configure a Digital Alarm

Configuring a digital alarm requires that you perform three actions.

Set the appropriate alarm flag in the PowerMonitor device.
Assign a meter tag to a PowerMonitor device for use with the digital alarm.
Create the digital alarm.

Set Alarm Flag in PowerMonitor Device

To use a digital alarm with a PowerMonitor device, you must set the appropriate alarm flag within the device. For this
example, Flag 3 is assigned to a voltage sag setpoint in the PowerMonitor 3000 device.

Follow these steps to configure alarm Flag 3 in the PowerMonitor 3000 module by using the PowerMonitor 3000 display
module. Refer to the

Setpoint Configuration

table on

page 165

for a list of setpoint parameters and user settings to use for

this example.

1.

Press the Escape key until DISP appears.

2.

Press the Down Arrow Key to select PROG mode.

3.

Press the Enter key to access Edit mode.

The display shows PASS.? with four flashing zeroes, 0000.

4.

Press the Up and Down arrow keys to select the four-digit password and press Enter.

The default password is 0000.

5.

Press the Down Arrow key to select CONFIGURATION, then press the Enter key.

6.

Press the Down Arrow key until you see SETPOINT, then press the Enter key.

7.

Press the Down Arrow key to select the setpoint number to configure, then press Enter key.

8.

Press the Down Arrow key to select a setpoint parameter.

The initial setpoint parameter is TYPE.

9.

Press Enter to access Edit mode.

10.

Press the Down Arrow key to select a value for the setpoint parameter.

For this example, VOLTAGE SAG is selected for the setpoint TYPE parameter.

11.

Press the Enter key to write the new value to the master module.

TIP

Refer to

Configure a PowerMonitor 3000 Device

on

page 57

for an overview of the PowerMonitor

3000 display module navigation menus.

TIP

For parameters that require numeric values, you can press and hold the Up Arrow or Down Arrow
key for a few seconds to increase the rate the value increments or decrements.