Chapter 12 Demand Control

System Application Guide

This section guides you through the pre-configured FactoryTalk View Machine Edition faceplate providing you with an
understanding of the status, control, and diagnostic operation of the faceplate display.

Faceplate Operation Overview

The Demand Control Faceplate opens with the Demand Control Status displayed.

Title Bar

Faceplate Toolbar

Load Status
Indicators

Close Button

Button

Icons

Description

Alarm

The alarm button indicates an alarm condition and activates alarm diagnostic views. A grey bell indicates normal

status, with no alarms. A red flashing bell indicates an alarm condition.

Configuration

The Configuration button displays the main demand control configuration screen (upon entering the correct

password).

Load 1…8

The Load 1-8 button lets you view the load status and descriptive name for loads 1…8

Load 9…16

The Load 9-16 button lets you view the load status and descriptive name for loads 9…16

Help

The Help button provides information for the existing view.

Close

Click the Close button to close the faceplate.

Status Indicators

Grey = Off/Normal Control
Green = On/Normal Control
D-Grey = Off/Demand Control
OVR-Grey = Off/Override Set
OVR-Green = On/Override Set
OVR-Red = On/Override Set/Operator Action Required
Red Flashing = Load is not in OVR, controller telling to turn off, but load is still on.
INT-Green = Interlocked On
INT-Grey = Interlocked Off

Interlocks Bypassed

Indicates that the interlocks have been bypassed for the load.

Predicted KW

Demand

The predicted KW demand is read from the PowerMonitor with the following color code

Red = Operator Action Required to stay within Demand kW Setpoint

Yellow = Shedding Loads to stay within Demand kW Setpoint

Green = Predicted Demand within Demand kW Setpoint - Shedding not required