FactoryTalk EnergyMetrix Software Reports and Charts Chapter 9

Standard Reports

FactoryTalk EnergyMetrix software standard reporting converts logged energy and production data into information you
can use to manage your business, improve efficiency, and reduce costs. You can run reports on demand, automatically on a
configured schedule, or event-driven in response to an alarm condition.

Standard Report Type

Description

Consumption

Reports all consumption values (for example, kWh, kVARh) for selected meters for a specified time interval. The report

groups meters as they are organized in the FactoryTalk EnergyMetrix software navigation tree, with subtotals calculated

for each group. The report includes all meters that have Consumption enabled for the value type.

Demand Analysis

Reports real power (for example kW) demand values for selected meters or groups for a specified time interval, and

itemizes each meter or group's contribution to the total. It also reports the worst case peak demand that would have

occurred had each meter or group’s peak demand occurred in the same demand interval. The report includes all meters

that have Demand enabled for the value type.

Billing

Generates a replication of a monthly bill (shadow bill) from your energy provider for comparative billing analysis and

potential energy cost recovery. The report is based on data from your energy meters and utility rate schedules. The

report is a list of line items and a total charge amount. Each line item consists of a description, quantity, rate and charge.

Cost Allocation

Runs a report that lists each meter's contribution to the total energy cost, based on a rate schedule that you configure.

Cost allocation reports are generated in Microsoft Excel output format.

Power Quality

Runs a report that combines a graph and a grid display of power quality, sag and swell events. This report is used only

for the PowerMonitor 3000 M6 and M8 models that have configured sag and swell setpoints. Enable PQ events logging

must be checked on the Device setup page. FactoryTalk EnergyMetrix software will periodically read the PowerMonitor

event log, and store sag and swell events in the database. Each sag and swell record lists the time, duration, and

maximum deviation of the sag or swell.

TIP

In addition to standard reports, the ReportsPlus option extends reporting capabilities by including custom script-
driven multipurpose, efficiency, load factor, power factor, and electrical summary reports.