Chapter 12 Demand Control

2.

Enter your configured password.

3.

Configure the demand control schedule, kW setpoint,
and billing end date.

For the Efficient Industries example, the demand control
is on from 8:00 to 18:00, Monday through Friday.

4.

Click on the load config button to configure the
individual loads.

For the efficient industries example, loads are configured
as follows:

Load

Description

Priority

Rated KW

On Delay SEC

Off Delay SEC

Max Off Time

SEC

1

Air Compressor 1

1

21

60

60

900

2

Air Compressor 2

1

21

60

60

900

3

AHU 1 Production

4

15

120

120

1800

4

AHU 2 Production

4

15

120

120

1800

5

AHU 3 Shipping

5

12

120

120

1800

6

AHU 4 Office

7

10

120

120

1800

7

Exhaust Fan 1

2

2

30

30

2700

8

Exhaust Fan 2

2

2

30

30

2700

9

Exhaust Fan 3

10

2

30

30

2700

10

Exhaust Fan 4

10

2

30

30

2700

11

Lighting Production 3

6

15

15

1200

12

Lighting Production 6

6

15

15

1200

13

Lighting Shipping

8

6

15

15

3600

14

Lighting Office

9

6

15

15

3600