318

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

Chapter 11

FactoryTalk View ME Energy Faceplates

6. Enter a module name for the first

PowerMonitor device.

For this example, you will configure the first
PowerMonitor device named
Electric_Main_PM3000.

7. Choose Input Data-REAL from the Comm

Format list.

8. Enter Connection Parameters.

9. Enter the IP address of the PowerMonitor device.

For this example, the Electric_Main_PM3000 IP address is 10.10.10.0.

10. Click OK.

11. Repeat steps 1…9 to configure each PowerMonitor 1000 and 3000 device in your project.

For the

Efficient Industries Plant 1

, enter the names and IP addresses of the PowerMonitor devices in the table. The

rest of the parameters in the New Module dialog box are the same.

When done, the I/O configuration should look like this.

Table 2 - PowerMonitor 1000/3000 Connection Parameters

Assembly Instance

Size

Input

1

16

Output

2

Configuration

3

0

PowerMonitor Device Name

IP Address

Electric_Main_PM3000

10.10.10.0

Boiler_House_PM1000

10.10.10.1

Power_House_PM1000

10.10.10.2

Production1_PM1000

10.10.10.3

Production2_PM1000

10.10.10.4

Shipping_Receiving_DC_PM1000

10.10.10.5

MCC2_PM1000

10.10.10.6