beautypg.com

Rockwell Automation Energy Management Accelerator Toolkit Quick Start User Manual

Page 165

background image

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014

165

FactoryTalk EnergyMetrix Software Alarm Setup Chapter 8

12.

Repeat steps 7…10 to edit the remaining setpoint parameters in the

Setpoint Configuration

table.

13.

Press the Escape key to return to PROG. or DISP. menus.

Repeat this procedure to configure other setpoints.

TIP

Refer to Bulletin 1404 PowerMonitor 3000 User Manual, publication

1404-UM001

for details on how to use data

messaging as an alternative for configuring PowerMonitor 3000 setpoints.

Setpoint Configuration

Parameter Name

Parameter Description

Range

Units

Default

Example Settings

Setpoint Number

The number of the setpoint being

configured.

1…10 (M4, M5)

1…20 (M6, M8)

-

N/A

1

Setpoint Type

The parameter value to be evaluated by

the setpoint.

0…52

(1)

(1) Refer to Bulletin 1404 PowerMonitor 3000 User Manual, publication

1404-UM001

or details on these settings.

-

0

VOLTAGE SAG

Setpoint Evaluation

Condition

The operator used to evaluate the

parameter value.

0 = Over forward (+)

1 = Over reverse (-)

2 = Under forward (+)

3 = Under reverse (-)

4 = Equal (=)

5 = Not equal (<>)

-

0

U. FWD.

Setpoint High Limit

The value being used as a reference to

activate the setpoint for over

comparisons, or to deactivate the setpoint

for under comparisons.

Note: This parameter is non-numeric

when viewed via the display module, and

the Setpoint Type is Phase Rotation or

Status input.

0…10,000,000

Depends on type

0

249

Setpoint Low Limit

The value being used as a reference to

deactivate the setpoint for over

comparisons, or to activate the setpoint

for under comparisons.

0…10,000,000

Depends on type

0

249

(2)

(2) This value is typically (line-to-neutral voltage -10%) for WYE systems and (line-to-line voltage -10%) for Delta systems.

Setpoint Action Delay

(Pickup Delay)

The minimum time in seconds that the

setpoint limit must be exceeded

continuously before the setpoint will

trigger.

0…3600

Sec (M4, M5)

0

0

0…30,000

0.1 Sec (M6, M8)

Setpoint Release Delay

(Dropout Delay)

The minimum time in seconds that the

setpoint limit must not be exceeded

continuously before the setpoint releases.

0…3600

Sec (M4, M5)

0

90

0…30,000

0.1 Sec (M6, M8)

Setpoint Action Type

The action that occurs when the setpoint

is triggered.

0…32

(1)

0

OUTPUT FLAG 3

Clear Accumulated

Time

Clear the time accumulator for this

setpoint

Yes

No

N/A

N/A