FactoryTalk View ME Energy Faceplates

Chapter 11

Configure RSLogix5000 for the E300 Module Faceplate

Follow these procedures to configure the faceplate.

Add the E300 Module to Your Ethernet Network

1. Create a new or open an existing RSLogix 5000 file.

2. Under I/O Configuration, right-click the network communication module to be used for the intended E300

module.

3. Select ‘New Module’.

4. Select the E300 Electronic Overload Relay Communication module (193-ECM-ETR) and click OK.

IMPORTANT

This step assumes you have already added and configured an Ethernet module to your I/O tree.

IMPORTANT

If this module is not available in the list, you can update the Add-on Profile for your device. Refer to Appendix E for more
information on updating the Add-on Profiles.