Yaskawa MP900 Series Machine Controller for Standard Operation User Manual
Page 481

A-5
A
Table A.4 CPHD_DRV_nnn
No free program memory space
(CPDH_CPU_0B3)
There is no free program memory
space.
• Compress memory from the System Defini-
tion Window.
• Reduce the size of all drawing and program
memory areas.
• Delete unused drawings or functions.
• Reduce the number of steps in each drawing
and function.
• Reduce the number of # registers in each
drawing and function.
• Reduce the number of symbols in each
drawing and function.
• Reduce the number of comments in each
drawing and function.
Another drawing or function calling the
function to be deleted
(CPDH_CPU_0C0)
Another drawing or function calls
the function that is being deleted.
Delete the instruction that is calling the func-
tion to be deleted, and then delete the func-
tion.
Data trace cannot be executed because
trace definition data number set to 0
(CPDH_CPU_0C1)
Data trace cannot be executed
because the trace definition data
number is set to 0.
Reset the trace definitions.
Disable coil number exceeded maximum
(100)
(CPDH_CPU_0C2)
The maximum number of disabled
coils (100) has been exceeded.
Reduce the number of disabled coils.
Flash memory write failure
(CPDH_CPU_0C3)
The write to flash memory pro-
cessing failed.
Repeat the operation.
Replace the Machine Controller if the error
persists.
Program write-protected
(CPDH_CPU_0F0)
The program is currently write-
protected.
Set the program to write-enabled mode using
the System Configuration Window.
Program memory not initialized
(CPDH_CPU_0F1)
The program memory has not
been initialized.
Clear the memory or perform batch load oper-
ation.
Program write-protected
(CPDH_CPU_0F0)
Program write protection in the
system definitions are set to dis-
able writing.
Change the write-protection setting in the
System Definitions Window and retry the
operation.
Error Message
Probable Cause
Possible Correction
Error Message
Probable Cause
Possible Correction
Interrupt level exceeds 0x0f.
(CPDH_DRV_002)
The designated interrupt level
range of 0 to 16 in the systems
definition file has been exceeded.
Set the interrupt level to between 0 and 16.
215IF I/F DIP switch 2 error
(CPDH_DRV_003)
There is an shared memory
address error in the system defini-
tions file.
Set a correct shared memory address.
Designated port number exceeds 1 to 6
range
(CPDH_DRV_005)
The designated port number is
greater than the range of 1 to 6.
Designate a correct port number.
215IF I/F DIP switch 3 error
(CPDH_DRV_007)
There is an shared memory
address error in the system defini-
tions file.
Set a correct shared memory address.