7 215if transmission definitions, Outline of 215if transmissions – Yaskawa MP900 Series Machine Controller for Standard Operation User Manual
Page 132

3.5 MP920 Module Definitions
3-37
3
Table 3.4 Start Register Address and Number of Words
Saving, Deleting, and Closing Generic Serial Definitions Data
Refer to the procedures in 3.3 Basic Individual Module Definition Operations for details.
3.5.7 215IF Transmission Definitions
This section explains how to define the 215IF transmission system.
Outline of 215IF Transmissions
The 215IF transmission system is a unique real-time Yaskawa network with transmission
speed 4 Mbps. Twisted-pair cable is used for the transmission lines, so an inexpensive but
highly reliable transmission system can be constructed.
The settings required for 215IF transmissions are divided into four tab pages: The Parame-
ter Settings, Link Assignments, I/O Map, and Status Tabs.
There are two kinds of transmissions in a 215IF Transmission System: Link transmissions
and message transmissions. The required settings for the link transmissions are made here.
Link transmissions are repeated every cycle according to the settings made here. Message
transmissions are programmed in drawing/function programs using the MSG-SND and
MSG-RCV functions.
Readout/Write-in of
Hold Register
With general-purpose serial communications, set the range and start
address of holding registers that can be read or written to using serial
communications. Refer to the table below for setting details.
Write-in width of Coil/
Hold Register
Set the range that can be written to of the coils and holding registers
as a whole.
Setting Item
Details
Setting Item
Machine Controller
MP920
CP-316
CP-316H
CP-916A
CP-916G
RIO-55
Readout of
Input Relay
Leading reg-
ister
IW0000
IW0000
IW0000
IW0000
IW0000
IW0000
No. of words
5120
6400
6400
2304
2304
2304
Readout of
Input
Register
Leading reg-
ister
IW0000
IW0000
IW0000
IW0000
IW0000
IW0000
No. of words
5120
6400
6400
2304
2304
2304
Readout/
Write-in Coil
Leading reg-
ister
MW00000
MW00000
MW00000
MW00000
MW00000
MW00000
No. of words
32768
8192
16384
3072
3072
3072
Readout/
Write-in Hold
Register
Leading reg-
ister
MW00000
MW00000
MW00000
MW00000
MW00000
MW00000
No. of words
32768
8192
16384
3072
3072
3072