Setting default values – Yaskawa MP900 Series Machine Controller for Standard Operation User Manual
Page 136
3.5 MP920 Module Definitions
3-41
3
∗
For parameter set values and network configuration, refer to the MP920
Machine Controller User's Manual: Communications Module (SIEZ-
C887-2.6).
Setting Default Values
The transmission parameters can be reset to their default values without inputting each
parameter, by selecting Edit (E) and then Default (S) from the 215IF Transmission Defini-
tions menu.
Table 3.6 Default Values of Transmission Parameters
Message Relay
Function
This setting determines whether the 215IF will receive messages
from another transmission interface and relay that message through
the 215IF interfaces, i.e., this setting enables or disables the Message
Relay Function.
When not using the Message Relay Function, set to "0." When using
the Message Relay Function, set to "1."
Message Relay Function
No. of Relayed
Network 1
When the Message Relay Function is enabled, this setting specifies
the range of network numbers (0 to 254) that can be relay destina-
tions. Messages will not be relayed to networks that are outside of
the specified range. The network number in the No. of Relayed Net-
work 1 setting is ORed with the network number in the No. of
Relayed Network 2 setting. The Relay Function will be disabled if
both settings are "0."
No. of Relayed
Network 2
See the explanation for the No. of Relayed Network 1 setting, above.
Maintenance Switch
These settings are all OFF during operation. These switches are used
for Yaskawa maintenance. Do not change the settings.
Parameter
Default
Own Station No.
0
Own Network No.
0
Token Cycle Time Setting
100
MEMOBUS Response Monitoring Time
0
Station Search Interval
0
Transmission Speed
4
Max No. of Stations Connected
16
Message Relay Function
0
No. of Relayed Network 1
0
No. of Relayed Network 2
0
Setting Item
Details
I /F
PLC
I /F
215IF
215IF
Enables/disables
the Relay Function.