Yaskawa MP900 Series Machine Controller for Standard Operation User Manual
Page 479

A-3
A
Table A.3 CPDH_CPU_nnn
AEND instruction structure incorrect
(CPDH_CMP_007)
The AEND instruction structure is
incorrect.
Match the number of ABOX or SBOX
instructions and AEND instructions in the
SFC Action Box Window.
Too many SFC flowchart steps
(CPDH_CMP_008)
The maximum number of steps in
the SFC flowchart has been
exceeded.
Reduce the number of SFC flowchart steps.
Too many SFC output bits
(CPDH_CMP_009)
The maximum number of SFC
output bits has been exceeded.
Reduce the number of SFC output bits to
within the permissible range.
ABOX instruction structure incorrect
(CPDH_CMP_010)
The ABOX instruction structure is
incorrect.
Correct the ABOX instruction and the rela-
tionship between ABOX and SBOX instruc-
tions.
SFC flowchart branches exceeded
(CPDH_CMP_012)
The number of SFC flowchart
branches has been exceeded.
Reduce the number of SFC flowchart
branches.
SFC flowchart structure incorrect
(CPDH_CMP_013)
The SFC flowchart structure is
incorrect.
Check the SFC flowchart for incorrect start,
end, or branch settings.
Too many SFC flowchart step boxes
(CPDH_CMP_014)
The number of SFC flowchart
step boxes has been exceeded.
Reduce the number of SFC flowchart step
boxes.
Expansion program (table or other
program) structure incorrect
(CPDH_CMP_015)
The table or other type expansion
program structure is incorrect.
Check the expansion program for incorrect
expansion program conversions in the CP-
717. Contact your Yaskawa representative if
the error persists.
Error Message
Probable Cause
Possible Correction
Error Message
Probable Cause
Possible Correction
1 DWG/FN object too large
(CPDH_CPU_021)
The size of one drawing or func-
tion object is too large.
Reduce the size of the drawing or function
objects.
Source memory control error
(CPDH_CPU_040)
A source memory control error
has occurred.
Execute the load again.
1 DWG/FN object too large
(CPDH_CPU_0B1)
The size of one drawing or func-
tion object file is too large.
Reduce the size of the drawing or function
objects.
Reduce the number of steps.
Reduce the number of # registers.
Machine Controller cannot run due to
program memory error or watchdog time
out
(CPDH_CPU_041)
The Machine Controller cannot
run due to a program memory
error or a watchdog time out.
Execute loading.
Cannot use this function because
Machine Controller is online
(CPDH_CPU_04D)
Load operation cannot be per-
formed because the Machine Con-
troller is online.
Stop Machine Controller operation using the
System Configuration Window.
Transmission error
(CPDH_CPU_090)
A transmission error has occurred.
• Repeat the operation.
• Check if the connectors are set properly.
• Check that there is no noise interference.
Incorrect processing request from CP-717
(CPDH_CPU_091)
There is an error in the processing
request from the CP-717.
Repeat the operation.
Replace the Machine Controller or CP-717 if
the error persists.
Incorrect processing request from CP-717
(CPDH_CPU_092)
There is an error in the processing
request from the CP-717.
Repeat the operation.
Replace the Machine Controller or CP-717 if
the error persists.