15 analog input definitions, Outline of the analog input definitions, Opening the analog input definitions window – Yaskawa MP900 Series Machine Controller for Standard Operation User Manual
Page 176

3.5 MP920 Module Definitions
3-81
3
Saving, Deleting, and Closing Counter I/O Definitions
Refer to the procedures in 3.3 Basic Individual Module Definition Operations for details.
3.5.15 Analog Input Definitions
This section explains how to set the Analog Input Definitions.
Outline of the Analog Input Definitions
The AI-01 Module is equipped with 8 analog input (AI) channels. The overall input circuit is
isolated, but the channels are not isolated from each other.
It is possible to use 1, 2, 4, or 8 channels. Processing speed can be improved by selecting
fewer channels because it is not necessary for the CPU to scan all 8 channels.
Input servicing is performed at fixed intervals, once for each scan (high-speed or low-speed)
in the CPU-01 Module. Each channel can be set to the high-speed or low-speed scan inde-
pendently.
Set the scan timing and allocates registers to 4 analog input channels in the Analog Input
Definitions Window.
Three types of analog input ranges must be selected.
Opening the Analog Input Definitions Window
Open the Analog Input Definitions Window according to the procedure in 3.3 Basic Individ-
ual Module Definition Operations.
CN1
Input
Port
S
ystem Bus Connector
S
ystem Bus
Interface
Isolation
Circuit
A/D
Convertor
Ana
log
m
u
lti
ple
xer