3.5 MP920 Module Definitions
3-85
3
Analog Output Definitions Window Original Menus
The following table shows the functions of the menu commands in the Analog Output Defi-
nitions Window.
Setting Analog Output Definitions
Setting Allocation Data
The Analog Output Definitions determine the operation and the disable status of the analog
outputs.
Menu Command
Function
Edit (E)
Assignment Delete (D)
Deletes allocation data.
Set (S)
Offset/Gain (O)
Sets the offset and gain.
Set Register (R)
Sets the register.
Setting Item
Details
Channel
Displays the channel number (1 to 4).
Out Range
(Output Range)
Selects the output range: -10 to +10 V or 0 to 10 V.
D
Controls the register's disable setting.
• :
Enabled
• :
Disabled
REG-No
Input the number of the register (O register number) that handles the
output.
Word (Number of
Words)
Displays the number of consecutive register words.
SCAN
Sets the transmission processing scan in which outputs are serviced.
• HIGH: High-speed scan
• LOW:
Low-speed scan
Output, Data
In online mode, these columns display the current value in the order
of current value, units, and hexadecimal current value of the
Machine Controller's register. The unit corresponds to the unit set in
Out Range.
A new current value input in the Output column can be stored in the
Machine Controller's register immediately by clicking the Set Button
or clicking Set (S) and then Set Register (R) on the Analog Output
Definitions menu.