I/o assignment tab page – Yaskawa MP900 Series Machine Controller for Standard Operation User Manual
Page 218

3.6 MP930 Module Definitions
3-123
3
I/O Assignment Tab Page
This tab page is used to set the I/O devices connected in the MECHATROLINK and their
transmission definition data.
Own Station Address
The MP930 is always a Master station, so the local station address is
fixed at 0 and cannot be changed.
Message Trust Level
Sets the error control method used when sending MEMOBUS com-
mands. In the MP930, the Message Trust Level is fixed at 1.
0
Send command just once and wait indefinitely for a response
from the destination.
1
Send command just once and resend if a response is not
received within 8 seconds.
2
When sending the command, send each word of data twice
consecutively and wait indefinitely for a response from the
destination. This method improves transmission quality but
reduces transmission efficiency by 50%.
Trans Cycle
The transmission cycle can be set to 2 ms only.
Transmission Speed: The transmission speed can be set to 4 Mbps
only.
Setting Item
Details
ST#
Displays the station number. Up to 14 stations can be set in the
MP930.
TYPE
Sets the type of I/O device connected at the station. Select an I/O
device type from the pull-down list.
D
Controls the input register's disable setting.
• :
Enabled
• :
Disabled
INPUT, SIZE
Sets the leading input register and number of registers (SIZE). The
number of registers is set automatically. Be sure that the range of
registers set for each station does not overlap with another station's
register numbers. The setting range for registers is determined by the
leading register number and ending register number set in the Mod-
ule Configuration Definition Window.
Setting Item
Details