P. 5-117 – Toa N-8000 Series User Manual
Page 527

Chapter 5
SYSTEM SETTINGS BY SOFTWARE
Direct Select: Contact Output
5-117
5.12.4. Contact output setting
Step 1. Click "Contact Output" tab to display the following setting screen.
Step 2. Set each item of "Contact output."
Set the access number for the contact output terminal to be activated when the station performs
external equipment control (one-shot make output or make/break output).
(1) Contact output No. (Can't be edited.)
The Direct select unit's contact output terminal number.
(2) Access No. digits
Select the number of digits to be used when controlling external equipment at the station.
(3) Access No.
Set the access number of the digit set in "Access No. digit", which is used to control external equipment at
the station.
Notes
• The access number cannot be set to "0."
• If the number of digits of the access number is 4, the usable numbers range from "0001" to "6144."
(4) Device
Enable or disable relay and LED outputs.
(5) line status
Select the line to be diagnosed.
The specified contact output terminal is closed when such status is judged abnormal that the CPU failure is
detected on the line or the line is not connected though the station number has been registered.
(6) Network status
Select the equipment to be diagnosed.
The specified contact output terminal is closed when the equipment is judged failed if no response is
detected from it.