Paging sync contact output control, Only when the n-8000mi/8000af is used), P. 2-182 – Toa N-8000 Series User Manual
Page 293

2-182
Chapter 2
FUNCTIONS AND OPERATION
OTHER FUNCTIONS (CONVENIENT FUNCTIONS)
8. PAGING SYNC CONTACT OUTPUT CONTROL
(only when the N-8000MI/8000AF is used)
The contact output of both the N-8000MI and N-8000AF interface units can be set as the paging output
destination. This makes it possible to control connected external equipment in synchronization with paging
activation.
Contact output destinations can be freely selected for up to 16 outputs for the N-8000MI and up to 8 outputs for
the N-8000AF. When the setting is performed so that only the contacts are included in a paging zone without
selecting audio paging output, only the contact outputs are activated and audio signals are not output at paging
initiation. Additionally, the closed contact status is also judged to be "busy." Therefore, while the contact output
is in use in a certain paging zone, if another page is initiated, it will only begin after the contact opens.
N-8000AF
Speaker
N-8000MI
LAN
Contact output
Paging operation
Revolving light