RUN/STOP Switch
Function Group
M1035
Number
Contents:
When M1035 = ON, PLC uses input point X7 as the switch of RUN/STOP.
COM Port Function
Function Group
Port
COM1
COM2
COM3
Item
Communication format
D1036
D1120
D1109
Number
Communication setting holding
M1138
M1120
M1136
ASCII/RTU mode
M1139
M1143
M1320
Slave communication address
D1121
D1255
Contents:
COM ports (COM1: RS-232, COM2: RS-485, COM3: RS-485) support communication format of
MODBUS ASCII/RTU modes. When RTU format is selected, the data length should be set as 8.
COM2 and COM3 support transmission speed up to 921kbps. COM1, COM2 and COM3 can be
used at the same time.
COM1:
Can be used in master or slave mode. Supports ASCII/RTU communication format, baudrate
(115200bps max), and modification on data length (data bits, parity bits, stop bits). D1036: COM1
(RS-232) communication protocol of master/slave PLC. (b8 - b15 are not used) Please refer to
table below for setting.
COM2:
Can be used in master or slave mode. Supports ASCII/RTU communication format, baudrate
(921kbps max), and modification on data length (data bits, parity bits, stop bits). D1120: COM2
(RS-485) communication protocol of master/slave PLC. Please refer to table below for setting.
COM3:
Can be used in master or slave mode. Supports ASCII/RTU communication format, baudrate
(921kbps max), and modification on data length (data bits, parity bits, stop bits). D1109: COM3
(RS-485) communication protocol of master/slave PLC. (b8 - b15 are not used) Please refer to
table below for setting.
Content
0: 7 data bits, 1: 8 data bits
b0 Data
Length
(RTU supports 8 data bits only)
00: None
01: Odd
b1
Parity bit
b2
11: Even
b3
Stop bits
0: 1 bit, 1: 2bits
0001(H1): 110
0010(H2): 150
b4
Baud rate
b5
b6
0011(H3): 300
2-62