beautypg.com

Delta DVP-ES2 User Manual

Page 242

background image

D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 1 2 6

¾

If DCNT instruction enables C243 as high speed counter (group A) and DHSC/DHSC

instruction uses C245 as high speed counter (group A) at the same time, PLC takes

C243 as the source counter automatically and no syntax check error will be detected.

¾

Table of settings for the high-speed interrupts of hardware counters and comparators:

(It is not applicable to DVP-SE.)

A group

B group

Hardware counter

A1 A2 A3 A4 B1 B2 B3 B4

Counter No.

C243, C245~C248, C251,C252 C244, C249, C250, C253, C254

High-speed counter

interrupt

I010 I020

I030

I040

I050

I060

I070 I080

High-speed compare

Set/Reset

Share 4 hardware

comparators for group A

Share 4 hardware

comparators for group B

¾

Table of settings for the high-speed interrupts of hardware counters and comparators:

(It is only applicable to DVP-SE.)

A group

B group

Hardware counter

A1 A2 B1 B2

Counter No.

C243, C245~C248, C251,C252

C244

High-speed counter

interrupt

I010 I020 I050 I060

Hi-speed compare

Set/Reset

Share 2 hardware

comparators for group A

Share 2 hardware

comparators for group B

¾

Block diagram of hardware counters and comparators:

Set /res et

Count
value

Count
value

Set /res et

Set /res et

Set /res et

Hardware
counter

Hardware
counter

Hardware
comparator

Hardware
comparator

A

A

B

B

A x 4

B x 4

B4

B1

A4

A1

A1

A4

B1

B4

I010

I040

I050

I080

7.

Difference between software and hardware comparators (it is not applicable to DVP-SE):

This manual is related to the following products: