4.1 Communication

Ports

DVP-ES2/EX2/SA2/SE/SX2 offers 3 communication ports (COM1~COM3), and DVP-SS2 offers 2

COM ports (COM1~COM2). COM ports of the above models support DELTA Q-link communication

format on HMI. Refresh rate of HMI can be increased by this function.

COM1: RS-232 communication port. COM1 can be used as master or slave and is the major COM port

for PLC programming. (It is not applicable to DVP-SE.)

COM2: RS-485 communication port. COM2 can be used as master or slave.

COM3 (ES2/EX2/SA2/SE): RS-485 communication port. COM3 can be used as master or slave. (For

DVP-ES2-C, COM3 is the CANopen port.)

COM3 (SX2): Conversion from the USB port to RS-232 port. COM3 can be used as slave only.

The 3 COM ports on the models mentioned above support Modbus ASCII or RTU communication

format.

USB (COM1) (SE): USB communication port. It only can be used as a slave. The communication

mode and format can not be modified.

Communication Format:

COM port

Parameter

RS-232

(COM1)

RS-485

(COM2)

RS-485

(COM3)

RS-485

(SX2 COM3)

Baud rate

110~115200 bps

110~921000 bps

110~115200 bps

Data length

7~8bits

Parity

Even / Odd / None parity check

Length of stop bit

1~2 bits

Register for Setting

D1036

D1120

D1109

Retain communication
format

M1138 M1120

M1136

ASCII mode

Available for both Master/Slave

Available for
Slave

RTU mode

Available for both Master/Slave

Available for
Slave

ASCII/RTU mode
selection

M1139 M1143

M1320

Communication address
of Slave

D1121 D1255

Data length for access
(ASCII)

100 registers

Data length for access
(RTU)

100 registers

Default communication settings for all COM ports:

− Modbus

ASCII

4 - 2

This manual is related to the following products: