2.9 S

Relay

Starting instruction in Sequential Function Chart (SFC).

S0~S9, total 10 points.

Initial step relay

Returns to zero point when using IST instruction in program. Zero

return step relays not used for IST instruction can be used as

general step relays.

S10~S19, total 10 ponits.

Zero return step relay

In sequential function chart (SFC), latched step relay will be saved

when power loss after running. The state of power on after power

loss will be the same as the sate before power loss.

S20 ~ S127, total 108 points.

Latched step relay

General relays in sequential function chart (SFC). They will be

cleared when power loss after running.

S128 ~ S911, total 784 points.

General purpose step relay

Used with alarm driving instruction API 46 ANS as an alarm

contact for recording the alarm messages or eliminating external

malfunctions.

S912 ~ S1023, total 112 points.

Alarm step relay


2.10 T (Timer)

The units of the timer are 1ms, 10ms and 100ms and the counting method is counting up. When

the present value in the timer equals the set value, the associated output coil will be ON. The set

value should be a K value in decimal and can be specified by the content of data register D.

The actual set time in the timer = timer resolution× set value

Ex: If set value is K200 and timer resolution is 10ms, the actual set time in timer will be 10ms*200 =
2000ms = 2 sec.

General Timer

The timer executes once when the program reaches END instruction. When TMR instruction is

executed, the timer coil will be ON when the current value reaches its preset value.

When X0 = ON, TMR instruction is driven. When current value achieves K100, the assocailte timer

contact T0 is ON to drive Y0. If X0 = OFFor the power is off, the current value in T0 will be cleared

as 0 and output Y0 driven by contact T0 will be OFF.

T0

Y0

X0

TMR

T0

K100

X0

T0

Y0

K100

10 sec

present
value

2-30