3 . I n s t r u c t i o n S e t
3 - 7
Program example:
Ladder diagram:
X0
Y1
X1
M0
X2
Y2
END
MPP
MRD
MPS
Instruction: Operation:
LD
X0
Load NO contact X0
MPS
Store current status
AND
X1
Connect NO contact X1 in series
OUT
Y1
Drive Y1 coil
MRD
Read the stored status
AND
X2
Connect NO contact X2 in series
OUT
M0
Drive M0 coil
MPP
Read the stored status and reset
OUT
Y2
Drive Y2 coil
END
End of program
Note: When compiling ladder diagram with WPLSoft, MPS, MRD and MPP will be automatically
added to the compiled results in instruction format. However, users programming in instruction
mode have to enter branch instructions as required.
Mnemonic Operands
Function
Program
steps
OUT
Y, M, S
Output coil
1~3
Controllers
ES2/EX2 SS2
SA2
SE
SA2
Explanations:
Output the program evaluation results before OUT instruction to the designated device.
Status of coil contact
OUT instruction
Associated Contacts
Evaluation result
Coil
NO contact(normal open)
NC contact(normal close)
FALSE
OFF
Current blocked
Current flows
TRUE
ON
Current flows
Current blocked
Program example:
Ladder diagram:
X0
X1
Y1
Instruction: Operation:
LDI
X0
Load NC contact X0
AND
X1
Connect NO contact X1 in series
OUT Y1
Drive Y1 coil