beautypg.com

Delta DVP-ES2 User Manual

Page 123

background image

3 . I n s t r u c t i o n S e t

3 - 7

Program example:

Ladder diagram:

X0

Y1

X1

M0

X2

Y2

END

MPP

MRD

MPS

Instruction: Operation:

LD

X0

Load NO contact X0

MPS

Store current status

AND

X1

Connect NO contact X1 in series

OUT

Y1

Drive Y1 coil

MRD

Read the stored status

AND

X2

Connect NO contact X2 in series

OUT

M0

Drive M0 coil

MPP

Read the stored status and reset

OUT

Y2

Drive Y2 coil

END

End of program

Note: When compiling ladder diagram with WPLSoft, MPS, MRD and MPP will be automatically

added to the compiled results in instruction format. However, users programming in instruction

mode have to enter branch instructions as required.

Mnemonic Operands

Function

Program

steps

OUT

Y, M, S

Output coil

1~3

Controllers

ES2/EX2 SS2

SA2

SE

SA2

Explanations:

Output the program evaluation results before OUT instruction to the designated device.

Status of coil contact

OUT instruction

Associated Contacts

Evaluation result

Coil

NO contactnormal open

NC contactnormal close

FALSE

OFF

Current blocked

Current flows

TRUE

ON

Current flows

Current blocked

Program example:

Ladder diagram:

X0

X1

Y1

Instruction: Operation:

LDI

X0

Load NC contact X0

AND

X1

Connect NO contact X1 in series

OUT Y1

Drive Y1 coil

This manual is related to the following products: