Page 449

background image

3 . I n s t r u c t i o n S e t

3 - 3 3 3

3.

In ASCII or RTU mode, when PLC’s COM2 sends out data, the data will be stored in

D1256~D1295. The feedback data will be stored in registers starting with S and converted into

D1296~D1311 in Hex automatically.

4.

Take the connection between PLC1 (PLC COM2) and PLC2(PLC COM1) for example, the

tables below explains the status when PLC1 reads Y0~Y17 of PLC2.

H87

MOV

M1002

D1120

SET

M1120

K100

MOV

D1129

RST

M1127

Set communication protocol as 9600, 8, E, 1

Retain communication protocol

Set communication timeout as 100ms

MODRW

K2

K1

X0

H0500

D0

K16

Connection device
address K1

Function code K2
read multiple bits

Data address Y0=H0500

Data storing register

Data length (bit)

Processing received data

ASCII mode: The received data is stored in registers starting from D0 in ASCII format and
PLC converts the content to

hexadecimal automatically.

registers D1296~D1311 in

RTU mode: The received data is stored in registers starting from D0 in Hex.

Reset M1127

M1127

SET

X0

M1122

Sending request

M1143 = OFF
ASCII mode

RST

M1143

M1143 = ON
RTU mode

SET

M1143

Receiving completed

ASCII Mode (M1143 = OFF):

When X0 = ON, MODRW instruction executes the function specified by Function Code 02.

PLC1

Ö PLC2,PLC1 sends: “01 02 0500 0010 E8

PLC2

ÖPLC1,PLC1 receives: “01 02 02 3412 B5

Registers for data to be sent (sending messages)

Register

Data

Descriptions

D1256 Low

‘0’

30 H

ADR 1

D1256 High

‘1’

31 H

ADR 0

Device address: ADR (1,0)

D1257 Low

‘0’

30 H

CMD 1

D1257 High

‘2’

32 H

CMD 0

Control parameter: CMD (1,0)

D1258 Low

‘0’

30 H

D1258 High

‘5’

35 H

D1259 Low

‘0’

30 H

D1259 High

‘0’

30 H

Y0 = H0500
Starting Data Address