beautypg.com

Delta DVP-ES2 User Manual

Page 93

background image

2 . P r o g r a m m i n g C o n c e p ts

DABSR:

1.

M1029= ON when instruction is completed.

2.

When the instruction is re-executed for the next time, M1029 will turn off first then ON again

when the instruction is completed

ZRN, DRVI, DRVA:

1.

M1029 will be “ON” after Y0 and Y1 pulse output is completed. M1102 will be “ON” after Y2

and Y3 pulse output is compeleted.

2.

When the instruction is re-executed for the next time, M1029 / M1102 will turn off first then

ON again when the instruction is completed.

Clear Instruction

Function Group

M1031, M1032

Number

Contents:

M1031 (clear non-latched memory) , M1032 (clear latched memory)

Device

Devices will be cleared

M1031

Contact status of Y, general-purpose M and general-purpose S
ƒ General-purpose contact and timing coil of T

Clear non-latched area

ƒ General-purpose contact, counting coil reset coil of C
ƒ General-purpose present value register of D
ƒ General-purpose present value register of T
ƒ General-purpose present value register of C

M1032

Contact status of M and S for latched

Clear latched area

ƒ Contact and timing coil of accumulative timer T
ƒ Contact and timing coil of high-speed counter C for latched
ƒ Present value register of D for latched
ƒ Present value register of accumulative timer T
ƒ Present value register of high-speed counter C for latched

Output State Latched in STOP mode

Function Group

M1033

Number

Contents:

When M1033 = ON, PLC outputs will be latched when PLC is switched from RUN to STOP.

Disabling all Y outputs

Function Group

M1034

Number

Contents:

When M1034 = ON, all outputs will turn off.

2 - 6 1

This manual is related to the following products: