7 C AN o p e n F u n c t i o n a n d O p e r a t i o n
7 - 1 7
Type: In SDO response message, 43 (Hex) refers to reading 4 bytes of data; 4B (Hex) refers
to reading 2 bytes of data; 4F (Hex) refers to reading 1 byte of data; 60 (Hex) refers to
writing 1/2/4 byte(s) of data; 80 (Hex) refers to stopping SDO command.
Example 1: Write 010203E8 (hex) to (Index_subindex) 2109_0 of slave of No. 3 through SDO
and the data type of (Index_subindex) 2109_0 is double words (32 bits).
Request
data:
Request message
PLC device
High byte(Hex)
Low byte(Hex)
D6250 ReqID=01 Command
=01
D6251
Reserved =0
Size =8
D6252
Message
Header
Type =02
Node ID =03
D6253
Main index high byte =21
Main index low byte =09
D6254
Reserved =0
Subindex =0
D6255
Datum 1=03
Datum 0=E8
D6256
Message
data
Datum 3=01
Datum 2=02
Response
data:
Response message
PLC device
High byte(Hex)
Low byte(Hex)
D6000 ResID
=01 Command
=01
D6001
Reserved =0
Size =4
D6002
Message
Header
Type =60
Node ID =03
D6003
Main index high byte =21
Main index low byte =09
D6004
Reserved =0
Subindex =0
D6005
Datum 1=00
Datum 0=00
D6006
Message
data
Datum 3=00
Datum 2=00
Example 2: Read the value of (Index_subindex) 2109_0 of slave of No. 3 through SDO and
the data type of (Index_subindex) 2109_0 is double words (32 bits).
Request
data:
Request message
PLC device
High byte(Hex)
Low byte(Hex)
D6250 ReqID
=01 Command
=01
D6251
Reserved =0
Size =4
D6252
Message
Header
Type =01
Node ID =03
D6253
Main index high byte =21
Main index low byte =09
D6254
Reserved =0
Subindex =0
D6255
Datum 1=0
Datum 0=0
D6256
Message
data
Datum 3=0
Datum 2=0