beautypg.com

1 common problems and solutions, Common problems and solutions -2 – Delta DVP-ES2 User Manual

Page 652

background image

D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

6-2

6.1 Common Problems and Solutions

The following tables list some common problems and troubleshooting procedures for the PLC system

in the event of faulty operation.

System Operation

Symptom

Troubleshooting and Corrective Actions

All LEDs are OFF

1.

Check the power supply wiring.

2.

Check If the power supplied to the PLC control units is in the range of

the rating.

3.

Be sure to check the fluctuation in the power supply.

4.

Disconnect the power supply wiring to the other devices if the power

supplied to the PLC control unit is shared with them.

If the LEDs on the PLC control unit turn ON at this moment, the

capacity of the power supply is not enough to control other devices

as well. Prepare another power supply for other devices or increase

the capacity of the power supply.

5.

If the POWER LED still does not light up when the power is on after

the above corrective actions, the PLC should be sent back to the

dealer or the distributor whom you purchased the product from.

ERROR LED is

flashing

1.

If the ERROR LED is flashing, the problem may be an invalid

commands, communication error, invalid operation, or missing

instructions, error indication is given by self-checking function and

corresponding error code and error step are stored in special

registers. The corresponding error codes can be read from the

WPLSoft or HPP. Error codes and error steps are stored in the

following special registers.

Error code: D1004

Error step: D1137

2.

If the connections between the PLC are failed and the LED will flash

rapidly, this indicates the DC24V power supply is down and please

check for possible DC24V overload.

3.

The LED will be steady if the program loop execution time is over the

preset time (set in D1000), check the programs or the WDT (Watch

Dog Timer). If the LED remains steady, download user program

again and then power up to see if the LED will be OFF. If not, please

check if there is any noise interference or any foreign object in the

PLC.

This manual is related to the following products: