D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-244

Device

No.

Function

Set-point range

Explanation

S

3

+1:

Proportional gain (K

P

) 0~30,000(%)

The proportion for

magnifying/minifying the error

between SV and PV.

Integration gain (K

I

) 0~30,000(%)

The proportion for

magnifying/minifying the integral

value (The accumulated error). For

control mode K0~K2, K5.

S

3

+2:

Integral time constant

(T

I

)

0~30,000 (ms)

For control mode K10

Derivative gain (K

D

)

-30,000~30,000

(%)

The proportion for

magnifying/minifying the derivative

value (The rate of change of the

process error). For control mode

K0~K2, K5.

S

3

+3:

Derivative time constant

(T

D

)

-30,000~30,000

(ms)

For control mode K10

S

3

+4:

Control mode

0: Automatic control

1: Forward control (E = SV - PV).

2: Reverse control (E = PV - SV).

5: Automatic mode with MV upper/lower bound control.

When MV reaches upper/lower bound, the

accumulation of integral value stops.

10: T

I

/ T

D

mode with MV upper/lower bound control.

When MV reaches upper/lower bound, the

accumulation of integral value stops.

S

3

+5,

6:

Tolerable range for error
(E), 32-bit

0~

2,147,483,647

E = the error between SV and PV.

If S

3

+5 is set as 5, when E is

between -5 and 5, E will be 0.

When S

3

+5 = K0, the function will

not be enabled.

S

3

+7,

8:

Upper bound of output
value (MV) , 32-bit

-2,147,483,648

~

2,147,483,647

Ex: if S

3

+6 is set as 1,000, MV will

be 1,000 when it exceeds 1,000.

S

3

+6 has to be bigger or equal to

S

3

+7, otherwise the upper bound

and lower bound value will switch