beautypg.com

Delta DVP-ES2 User Manual

Page 67

background image

2 . P r o g r a m m i n g C o n c e p ts

Applicable Hardware High Speed Counters:

1-phase

input

1-phase 2-input

2-phase 2-input

C

X

C243 C244 C245 C246 C247 C248 C249 C250 C251 C252 C253 C254

X0 U

U/D

U/D

U

U A

A

X1 R

Dir

Dir

D

D B

B

X2 U

U/D

U/D

A

A

X3 R

Dir

Dir

B

B

X4

R R R

X5

R

R

U: Count up

A: Phase A input

Dir: Directoin signal input

D: Count down

B: Phase B input

R:

Reset signal input

Note:

1.

The max frequency of the 1-phase input counters X0 (C243) and X2(C244) is 100kHz on

ES2/EX2/SA2/SX2 model and 20kHz on SS2 model.

2.

The max frequency of the 1-phase 2-input counters (X0, X1)(C245, C246) and (X2, X3)(C249,

C250) is 100kHz on ES2/EX2/SA2/SX2 model and 20kHz on SS2 model.

3.

The max frequency of the 1-phase 2-input counters (X0, X1)(C247, C248) is 10kHz on

ES2/EX2/SS2/SX2 model and 100kHz on 32ES211T and SA2 model..

4.

The max frequency of the 2-phase 2-input counter (X0, X1)(C251, C252) is 5kHz on ES2/EX2

model, 10kHz on SS2/SX2 model and 50kHz on 32ES211T and SA2 model.

5.

The max frequency of the 2-phase 2-input counter (X2, X3)(C253, C254) is 5kHz on

ES2/EX2/SA2 model, 10 kHz on SS2/SX2 model and 50kHz on 32ES211T.

6.

2-phase 2-input counting supports double and 4 times frequency, which is selected in D1022

as the table in next page. Please refer to the below table for detailed counting wave form.

D1022

Counting mode

A

B

up co

unt

down

coun

t

A

B

up co

unt

down

coun

t

K2

(Double Frequency)

A

B

up

co

un

t

dow

n co

unt

A

B

up

co

un

t

dow

n co

unt

K4 or other value

(Quadruple frequency)

(Default)

2 - 3 5

This manual is related to the following products: