3 . I n s t r u c t i o n S e t
3 - 2 7 5
Registers for received data (responding messages)
Register
Data
Descriptions
D1070 low
‘0’
30 H
ADR 1
D1070 high
‘1’
31 H
ADR 0
D1071 low
‘0’
30 H
CMD 1
D1071 high
‘6’
36 H
CMD 0
D1072 low
‘0’
30 H
D1072 high
‘1’
31 H
D1073 low
‘0’
30 H
D1073 high
‘0’
30 H
Data address
D1074 low
‘1’
31 H
D1074 high
‘7’
37 H
D1075 low
‘7’
37 H
D1075 high
‘0’
30 H
Data content
D1076 low
‘7’
37 H
LRC CHK 1
D1076 high
‘1’
31 H
LRC CHK 0
Program Example 2:
Communication between PLC and VFD-B series AC motor drives (RTU Mode, M1143 = ON)
MOV
D1120
H87
M1002
SET
M1120
Set communication protocol as 9600, 8, E, 1
Retain communication protocol
Set receiving timeout as 100ms
Sending request
X1
M1127
RST
M1127
Receiving
completed
Process of receiving data
Reset M1127
The receiving data is stored in
D1070~D1085 in Hex.
Set as RTU mode
X0
Set communication instruction:
Data address: H2000
Write in data H12
Device address: 01
MOV
D1129
K100
SET
M1143
SET
M1122
MODWR
H2000
K1
H12
PLC
→ VFD-B, PLC transmits: 01 06 2000 0012 02 07
VFD-B
→ PLC, PLC receives: 01 06 2000 0012 02 07