3 . I n s t r u c t i o n S e t

3 - 2 7 5

Registers for received data (responding messages)

Register

Data

Descriptions

D1070 low

‘0’

30 H

ADR 1

D1070 high

‘1’

31 H

ADR 0

D1071 low

‘0’

30 H

CMD 1

D1071 high

‘6’

36 H

CMD 0

D1072 low

‘0’

30 H

D1072 high

‘1’

31 H

D1073 low

‘0’

30 H

D1073 high

‘0’

30 H

Data address

D1074 low

‘1’

31 H

D1074 high

‘7’

37 H

D1075 low

‘7’

37 H

D1075 high

‘0’

30 H

Data content

D1076 low

‘7’

37 H

LRC CHK 1

D1076 high

‘1’

31 H

LRC CHK 0

Program Example 2:

Communication between PLC and VFD-B series AC motor drives (RTU Mode, M1143 = ON)

MOV

D1120

H87

M1002

SET

M1120

Set communication protocol as 9600, 8, E, 1

Retain communication protocol

Set receiving timeout as 100ms

Sending request

X1

M1127

RST

M1127

Receiving
completed

Process of receiving data

Reset M1127

The receiving data is stored in
D1070~D1085 in Hex.

Set as RTU mode

X0

Set communication instruction:

Data address: H2000

Write in data H12

Device address: 01

MOV

D1129

K100

SET

M1143

SET

M1122

MODWR

H2000

K1

H12

PLC

→ VFD-B, PLC transmits: 01 06 2000 0012 02 07

VFD-B

→ PLC, PLC receives: 01 06 2000 0012 02 07