beautypg.com

Delta DVP-ES2 User Manual

Page 124

background image

D V P - E S 2 / S A 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3 - 8

Mnemonic Operands

Function

Program

steps

SET

Y, M, S

Latches the ON
status

1~3

Controllers

ES2/EX2 SS2

SA2

SE

SX2

Explanations:

When the SET instruction is driven, its designated device will be ON and latched whether the SET

instruction is still driven. In this case, RST instruction can be applied to turn off the device.

Program example:

Ladder Diagram:

X0

Y0

Y1

SET

Instruction: Operation:

LD

X0

Load NO contact X0

ANI

Y0

Connect NC contact Y0 in series

SET Y1 Drive Y1 and latch the status

Mnemonic Operands

Function Program

steps

RST

Y, M, S, T, C, D, E,

F

Resets contacts,
registers or coils

3

Controllers

ES2/EX2 SS2

SA2

SE

SX2

Explanations:

Device status when RST instruction is driven:

Device

Status

S, Y, M

Coil and contact are set to OFF.

T, C

Current value is cleared. Associated contacts or coils are reset .

D, E, F

The content is set to 0.

Status of designated devices remains the same when RST instruction is not executed.

Program example:

Ladder diagram:

X0

Y5

RST

Instruction: Operation:

LD

X0

Load NO contact X0

RST Y5 Reset contact Y5

Mnemonic Operands

Function

Program

steps

MC/MCR

N0~N7

Master control
Start/Reset

3

Controllers

ES2/EX2 SS2

SA2

SE

SX2

Explanations:

MC is the master-control start instruction. When MC instruction executes, the program execution

turns to the designated nest level and executes the instructions between MC and MCR. However,

MCR is the master-control reset instruction placed at the end of the designated nest level and no

drive contact is required before MCR. When MC/MCR is not active, devices and instructions

This manual is related to the following products: