beautypg.com

Delta DVP-ES2 User Manual

Page 383

background image

3 . I n s t r u c t i o n S e t

3 - 2 6 7

API Mnemonic Operands

Function

99

PLF

Falling-edge output

Controllers

ES2/EX2 SS2 SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

S

*

*

PLF: 3 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S: Falling pulse output device

Explanations:

When X0 goes from ON to OFF (Falling-edge trigger), PLS instruction executes and S generates a

cycle pulse for one operation cycle.

Program Example:

Ladder Diagram:

X0

M0

PLF

M0

Y0

SET

Timing Diagram:

A scan cycle

X0

M0

Y0

Instruction

Code: Operation:

LD

X0

;

Load

NO

contact

X0

PLF

M0

; M0 falling-edge output

LD

M0

;

Load

NO

contact

M0

SET

Y0

;

Y0

latched