Program Example 1:

Communication between PLC and VFD-B series AC motor drives (ASCII Mode, M1143 = OFF)

MOV

D1120

H87

M1002

SET

M1120

M1127

RST

M1127

Receiving
completed

Set communication protocol as 9600, 8, E, 1

Retain communication protocol

Set receiving timeout as 100ms

Processing received data

Reset M1127

Sending request

X1

X0

Set communication instruction:

Data address: H0100

Data: H1770

Device address: 01

The received data is stored in
D1070~D1085 in ASCII format.

MOV

D1129

K100

SET

M1122

MODWR

H0100

K1

H1770

PLC

→ VFD-B, PLC transmits: “01 06 0100 1770 71 ”

VFD-B

→ PLC, PLC receives: “01 06 0100 1770 71 ”

Registers for data to be sent (sending messages)

Register

Data

Descriptions

D1089 low

‘0’

30 H

ADR 1

D1089 high

‘1’

31 H

ADR 0

Address of AC motor drive: ADR
(1,0)

D1090 low

‘0’

30 H

CMD 1

D1090 high

‘6’

36 H

CMD 0

Command code of AC motor
drive: CMD (1,0)

D1091 low

‘0’

30 H

D1091 high

‘1’

31 H

D1092 low

‘0’

30 H

D1092 high

‘0’

30 H

Data address

D1093 low

‘1’

31 H

D1093 high

‘7’

37 H

D1094 low

‘7’

37 H

D1094 high

‘0’

30 H

Data contents

D1095 low

‘7’

37 H

LRC CHK 1

D1095 high

‘1’

31 H

LRC CHK 0

Checksum: LRC CHK (0,1)